diane, in the ac breaker box disconnect the ground wire from where it is touching the black wire that is acting as your common wire. I believe you have a floating neutral inverter they cannot be hooked up that way. Neutral and ground wire must be seperate in the ac breaker box.Diane Maldonado wrote:Ok I took some videos of my set up. Hopefully its more clear what is happening with the inverter. We tested the load (input) going into the inverter and it worked fine but the voltage output on inverter is not converting. Thanks in advance.
I can't up load movies so I posted them on youtube.
This is the solar panel mount video:
https://www.youtube.com/watch?v=REIL8tyHBBs
This is the battery set up
https://www.youtube.com/watch?v=MwwBqOgzp60
This is the inverter
https://www.youtube.com/watch?v=0nsZmHFkD8I