Cristobal Cristo wrote:I already commented on this issue stating that there exist quality differences between various IFBs, but now I'm thinking that they should not be used in the wood flame path.
Two vendors/manufactures that I inquired about IFB use in flame path said it was OK, but at the same time it's rather obvious that they are not intended for wood flame path:
1. IFBs are rather new invention, established in industry in the 50s.
2. Industry uses natural gas, propane or electricity to melt, crack, kiln fire.
3. If wood is burnt in biomass power stations or incinerators - high alumina hard bricks are used (I read some paper), because amount of fluxes and detrimental substances is high.
I remember and fully agree now. This is one of the reasons for my posting of the final results as they have often been recommended to use in locations just like I did. I am not blaming a soul, just reporting the end results after 3 years of hard burning.
Cristobal Cristo wrote:
My electric ceramic kiln is lined with IFB26, but it's electric and only I converted it to propane and propane exhaust is super clean compared to wood and I use it maybe 10 times per year only, so I may not be able to notice any deterioration.
I just read that IFB/propane kilns may have longevity of 1-5 years in high use environment. High use for ceramics firing would be once per 3 days, because cooling to less than 50 C (safe for glazes) takes me around 40 hours. For quick raku firing (objects are removed hot from the kiln) firings could be more frequent with much more thermal strees.
Masonry heater will be probably fired for let's say 4 months, so with one fire par day it's 120 firings - eauivalent to once per 3 days kiln use schedule. However the fuel is wood with chlorine (bricks don't like it) and various fluxes. Also the temperature in properly built riser is equal and turbulence much higher than in a kiln.
So it looks like IFBs in wood flame path are really being tested by us. I'm really curious about performance of IFB risers built by others.
Excellent deduction for the cause of the problem and end results. While no one has asked, this was not a expansion limiting layup of bricks. Unless they could have walked, I will never know now. But I am doubting it, as the perfectly undamaged bricks were just below and besides the IFB's
Thank you Cristobal Cristo for possible root of the cause. I would like to add one thing concerning propane heat, and cinder block only flues using standard mortar, this has been known to cause problems. Though I am not sure the root of the cause. Some flues, as in my case, had cast high clay liners that are working just fine after 67 years, (no propane every used, simply wood stoves all these years)